QSP-120 Multi-Hazard Suppression Control Panel

INDUSTRY China
Check with seller  

Description

Characteristics
Panel and manual pull station count-down simultaneously.
Discharge delay timer setting (20 ~ 999 seconds).
Cross-zone detection confirmation makes better stability.
Built-in phone jacks on both panel and manual pull station.
Expandable to 5 cross-zone detection sections.
Each section has manual/auto operation mode.
Wiring trouble inspection.
Through dipswitch to select the supervision on feed-back signal of agent discharge.
All 24V output contacts are protected by fuse.

Specifications
Model QSP-120
Power 220V AC 50/60Hz *Others also available
Battery Capacity 1 cross-zone: 24V DC 1.2Ah
5 cross-zone: 24V DC 4Ah
Zone Voltage 24V DC
EOL Resistance 4.7kΩ
Detection Type Cross-zone detection
# of heat detectors connected No limit *Except electronic-type
# of smoke detector connected 25/zone *Horing Lih manufactured
Dimensions (mm) H x W x D 1 cross-zone: 350 x 400 x 130
5 cross-zone: 550 x 400 x 130
Color Ivory